LeaXield detects the common-mode currents on the load-side via a current sensing transformer. An amplifier generates an inverse of the leakage currents and feeds them to the power line via a capacitor network. This produces almost complete cancellation of the leakage currents. LeaXield is now designed for rated currents of up to 150 A for 3-phase grids at frequencies of 50/60 Hz and a rated voltage of 520 V AC. The new active filter can be used in systems with leakage currents of up to 1000 mA.
Besides minimizing earth leakage currents, LeaXield active filter modules can also improve the EMC performance of power drive systems in the range up to around 500 kHz. The new active filter module achieves typical common-mode attenuation values of up to 30 dB at 4 kHz, 40 dB at 10 kHz, and 15 dB at 150 kHz.
The EPCOS LeaXield module can be retrofitted into existing converter-based installations in order to improve their EMC and the RCD compatibility of the power drive system. Moreover, LeaXield circuits can be integrated into new EMC filter solutions in order to downsize the expensive current-compensated filter chokes.
Main applications
- Power drive systems with frequency converters and long motor cables
Main features and benefits
- Compensation of earth leakage currents up to 1000 mA
- Improved common-mode attenuation in the frequency range from 4 kHz to approximately 500 kHz